• Tel: 086-577-61717596
  • E-mail: info@chyf.com
  •   ZW32M-12 Series Outdoor High Voltage Permanent Magnet Vacuum Circuit Breaker
  • {content:title}

ZW32M-12 Series Outdoor High Voltage Permanent Magnet Vacuum Circuit Breaker

Model: ZW32M-12

Description:

The circuit breaker is mainly used for breaking and closing the load current, overload current and short- -circuit current in the power system.
It is suitable for protection and control in substation and industrial and mining enterprise power distribution system, and the place where rural power grid needs frequent operation.
Accept OEM&ODM:YES
Certificate: CE,Test reports
Production time: 7~ 12 working days
Warranty period: 12 Months
Delivery time: 15 days
Payment term: 50% deposit before production+50% balance before shipment(by T/T,D/P,Paypal)
  • General
  • Technical Parameter
  • ZW32M-12 outdoor permanent magnet high voltage AC vacuum circuit breaker (hereinafter called smart switch) consists of ZW32-12/T630-20 outdoor high voltage vacuum circuit breaker, reclosing controller, external voltage transformer and control cable. The smart switch is an outdoor high- -voltage power distribution switchgear device with rated voltage of 12 KV and three- -phase AC of 50 Hz. The circuit breaker is mainly used for breaking and closing the load current, overload current and short- -circuit current in the power system. It is suitable for protection and control in substation and industrial and mining enterprise power distribution system, and the place where rural power grid needs frequent operation. The smart switch complies with GB 1894 -2003 "High Voltage AC Circuit Breaker" and GB/T 7261-2008 "Basic Test Methods for Relay Protection and Safety Automatic Devices" and other standards.

    Model Meaning

    Working Condition

    O Ambient air temperature: Max. +45C ,Min.-40%C. O Altitude:≤3000m. O Wind speed: Not more than 34m/s. O Relative Air Humidity: Daily average is not greater than 90%, month average is not greater than 90%. O Pollution level: Not more than IV. O lcing thickness:≤10mm. O Installation site: should be no fire, explosion hazard, chemical corrosion and severe vibration,etc.

    Drawing

    Environmental

  • No Item Unit Data
    1   Rated voltage KV 12
    2   Rated current A 630
    3   Rated frequency Hz 50
    4   Rated insulation level 1 min power frequency withstand voltage (to earth, phase to phase,between open contacts)   Dry test KV 42/48(Between open contacts)
      Wet test 34
    Secondary circuit to earth 2
    Lightning impulse withstand voltage (peak) 75/85(Between open contacts)
    5   Rated short circuit breaking current KA 20
    6   Rated short-circuit closing current (peak) KA 50
    7   Rated short-circuit withstand current KA 20
    8   Rated peak withstand current KA 50
    9   Rated short-circuit breaking current breaking times Times 30
    10   Rated short circuit duration S 4
    11   Rated operating voltage and auxiliary voltage V DC220 or AC220
    12   Rated operating sequence O-0.3s-CO-180s-CO
    13   Overcurrent release rated current A 5
    14   Mechanical life Times 10000
Copyright@2023 Yufeng Electric Co.,Ltd All Rights Reserved