Button |
Pushing in |
The controller allows operation.After pressing the button:
1.When the system is in the standby state,the motor will start to move to the working position;
2.When the system is in the working position,the command will not be responded |
Pushing ou |
The controller allows operation.After pressing the button:
1.When the system is in the standby state,the motor will start to move to the test position;
2.When the system is in the test position,the command will not be responded |
Emergency
stop/reset |
When the controller is in the lock state for protection,red protection indicator on the panel lights up,pressing
the button will let the system return to standby state.If the button is pressed while the system is in the working
position or the test position,the motor will immediately be braked and return to standby state |
Indicator
lamp |
Power supply |
Power indicator that will go on and is green at power on,and go off at power off |
Ready |
Ready indicator that will go on and is green at ready,and go off if not |
Remote |
Remote operation indicator that will go on and is white in remote mode,and go off in local mode |
Work position |
Normally on and is red when the electric mechanism is in work position |
Test position |
Normally on and is red when the electric mechanism is in test position |
Fault |
Normally on and is red when the system protection lock starts,and go off when it is reset. |
1 |
Power L/+ |
Positive or L controller power supply |
2 |
Power N/- |
Negative or N controller power supply |
3 |
Motor + |
Driving signal output of controller,connect to driving motor “+” |
4 |
Motor- |
Driving signal output of controller,connect to driving motor“- ” |
5.6 |
Fault alarm |
NO contact.Open when there is no locked rotor fault,and close when there is locked rotor fault |
7 |
Remote |
It is remote operation mode when it is short-circuit connected with the common port of digital input |
8 |
Remote reset |
Effective when it is short-circuit connected with the common port of digital input |
9 |
Interlock input |
Effective when it is short-circuit connected with the common port of digital input |
10 |
Manual prior |
It is manual operation mode when it is short-circuit connected with the common port of digital input,and is
electric operation mode when it is disconnected with the common port of digital input; |
11 |
Local |
It is local operation mode when it is connected with the common port of digital input; |
12 |
Local pushing in |
Effective when it is short-circuit connected with the common port of digital input |
13 |
Local pushing ou |
Effective when it is short-circuit connected with the common port of digital input |
14 |
Remote pushing in |
Effective when it is short-circuit connected with the common port of digital input |
15 |
Remote pulling out |
Effective when it is short-circuit connected with the common port of digital input |
16 |
Work posilion |
Effective when it is short-circuit connected with the common port of digital input |
17 |
Test position |
Effective when it is short-circuit connected with the common port of digital input |
18 |
Common port |
Common port of digital input signal |
P+ |
|
485 communication port |
N- |
|
GDN |
|