Description:
Its high-life vacuum interrupter and epoxy casting sealing technology ensuremaintenance-free integrated solid-sealed poles,and high-reliability permanent mognet operaling mechanismensures maintenance-free operation of the operating mechanism. Main advantages Safe and reliable, able to meet operational requirements under special conditions Over 22 years of manufacturing experience Brand vacuum arc extinguishing chamber and fixed sealing pole Reliable operating mechanism Excellent operational system ensures stable quality and convenient delivery Complete solutions, convenient ordering, and easy installation Accept OEM&ODM:YES Certificate: CE,Test reports Production time: 7~ 12 working days Warranty period: 12 MonthsNo. | Item | Unit | Data | ||||
1 | Rated voltage | KV | 12 | ||||
2 | Max.working voltage | KV | 12 | ||||
3 | Rated current | A | 630 1250 | 630 1250 1600 2000 2500 3150 | 1250 1600 2000 2500 3150 4000 | ||
4 | Rated short circuit breaking current (Rated thermal stability current (RMS)) | KA | 20/25 | 31.5 | 40 | ||
5 | Rated short-circuit current (peak) | KA | 50/63 | 80 | 100 | ||
6 | Rated dynamic stability current (peak) | KA | 50/63 | 80 | 100 | ||
7 | 4S Rated withstand current | KA | 20/25 | 31.5 | 40 | ||
8 | Rated insulation level | Power frequency withstand voltage (rated breaking before and after)/1 min power frequency withstand voltage | KV | To earth 42 (Between open contacts) | |||
Impulse withstand voltage(rated breaking before and after)/Lightning impulse withstand voltage (peak) | To earth 75 (Between open contacts | ||||||
9 | Rated thermal stability time | S | 4 | ||||
10 | Rated operating sequence | O-0.3S-CO-180S-CO | |||||
11 | Mechanical life | Times | 20000 | ||||
12 | Rated short circuit current breaking time | Times | 50 | ||||
13 | Rated operating mechanism closing voltage (DC) | V | AC、DC 110,220 | ||||
14 | Actuator voltage of the floodgate (DC | V | AC、DC 110,220 | ||||
15 | Contact stroke | mm | 11±1 | ||||
16 | Overtravel(the length of contact spring compression) | mm | 3.5±0.5 | ||||
17 | Three-phase points,closing phase asynchronous | Ms | ≤2 | ||||
18 | Contact closing bounce time | ms | ≤2 | ||||
19 | Average opening speed | m/s | 0.9~1.2 | ||||
Average closing speed | m/s | 0.5~0.8 | |||||
20 | Opening time | Under max.operating voltage | S | ≤0.05 | |||
21 | Under min.operating voltage | ≤0.08 | |||||
22 | Closing time | S | 0.1 | ||||
23 | The main circuit resistance of each phase | μΩ | 630≤50 | 1250≤45 | |||
24 | Allowed comision thickness for fixed and movable contacts | mm | 3 |