• Tel: 086-577-61717596
  • E-mail: info@chyf.com
  •   FKN12A-12 Indoor High Voltage Vacuum Load Break Switch LBS with Fuse Link
  • {content:title}

FKN12A-12 Indoor High Voltage Vacuum Load Break Switch LBS with Fuse Link

Model: FKN12A-12

Description:

It matches an earthing switch with the ability to close short-circuit current. The operating mechanism can be divided into manual and electric type, which is convenient for realizing the three remote control requirements of the power system.

Working Condition


O Altitude: 1000m.
O Ambient air temperature: Max.+40*C; Min.- 25C (Allowed to storage and transportation at - -30°C).
O Air relative humidity: Daily average is not greater than 95%, monthly average is not greater than 90%.
O Pollution level: I.
O Seismic intensity: Not more than 8 degree.
O No frequent and severe vibration.
O The surrounding air is not contaminated by corrosive or flammable  gases, water vapor, etc.
  • General
  • Technical Parameter
  • FZN25- .12DL/T630- -20 indoor AC high voltage vacuum load switch is an indoor unit with three- phase AC of 50Hz, 12KV rated voltage, applicable to industrial and mining enterprises' power distribution stations and substations, etc. As the protection and control of electrical facilities, it is used for opening and closing load current, closed loop current, no-load transformer and cable charging current. It matches an earthing switch with the ability to close short-circuit current. The operating mechanism can be divided into manual and electric type, which is convenient for realizing the three remote control requirements of the power system. FZR25-12DL/T200-31.5 indoor AC high voltage vacuum load switch- fuse combination is an indoor unit with three- phase AC of 50Hz, 12KV rated voltage, applicable to industrial and mining enterprises' power distribution stations and substations, etc., as short circuit protection and load control. It matches an earthing switch with ability to close short- -circuit current.The operating mechanism can be divided into manual and electric type,which is convenient for realizing the three remote control requirements of the power system.

    Working Condition

    O Altitude: 1000m. O Ambient air temperature: Max.+40*C; Min.- 25C (Allowed to storage and transportation at - -30°C). O Air relative humidity: Daily average is not greater than 95%, monthly average is not greater than 90%. O Pollution level: I. O Seismic intensity: Not more than 8 degree. O No frequent and severe vibration. O The surrounding air is not contaminated by corrosive or flammable  gases, water vapor, etc.  

    Drawing

    Environmental

  • No. Item Unit Data
    FZN25-12DL/T630-20 FZRN25-12DL/T20O-31.5
    Rated voltage KV 12
    2 Rated current A 630 200
    3 Rated frequency HZ 50
    4 Rated insulation level 1 min power frequency withstand voltage KV Arc chamber between open contacts 30;To earth,phase to phase 42 lsolation between open contacts 48
    Lightning impulse withstand voltage KV To earth,phase to phase 75;Isolation between open contact 85
    5 Rated short-time withstand current KA 20
    6 Rated short circuit duration S 4
    7 Rated peak withstand current KA 50
    8 Rated active load breaking current A 630
    9 Rated closed-loop breaking current A 630
    10 Rated cable charging breaking current A 10
    11 Rated breaking no-load transformer capacity KVA 1600
    12 Rated short-circuit breaking current KA 31.5
    13 Rated transfer current A 2000
    14 Fuse type SDLAJ-12、XPNT1-12
    15 Impactor output energy J 1+0.5
    16 Rated short circuit closing current KA 80 (Expected peak)
    17 Earthing switch rated short-time withstand current KA 20
    18 Earthing switch rated short circuit duration S 2
    19 Earthing switch rated peak withstand current KA 50
    20 Auxiliary circuit rated voltage V ≌ 220V、≌ 110V
    21 Mechanical life Times 10000
Copyright@2023 Yufeng Electric Co.,Ltd All Rights Reserved